heatpumpsforbusinesses

Heat Pump vs Gas Boiler for Business Premises

A side-by-side comparison of a commercial heat pump and a gas boiler, with the running-cost break-even worked through.

Independent information, not installer advice. Last reviewed 8 October 2026. Sources are linked in the text.

The comparison at a glance

FactorCommercial heat pumpGas boiler
Capital costGenerally higher; published bands run from £55,000 for a 100 kW thermal air-source system, and ancillaries add to itGenerally lower for like-for-like output
Running-cost driverElectricity price divided by SCOPGas price divided by boiler efficiency
MaintenanceRefrigerant circuit, fans, controls; annual servicing quoted from about £250 plus VAT in one installer guideBurner, heat exchanger, flue; routine annual service
CarbonDepends on grid carbon intensity and SCOPFixed by the fuel burned
ResilienceDepends on electricity supply; gas back-up possible in a hybridDepends on gas supply
Space and sitingOutdoor units, buffer vessels, possible plant room changesCompact plant room and flue
NoiseFan noise outdoors; a planning noise assessment is commonly requestedUsually low external noise
FundingBUS grant if 45 kW thermal or less for a single heat pump (70 kW thermal for a multi-unit system) in England or Wales; capital allowancesCapital allowances may apply; no heat pump grant

Treat the table as a framework, not a verdict. The next sections explain the rows that decide most cases.

Running cost: where the arithmetic bites

DESNZ’s Q1 2026 Quarterly Energy Prices (provisional, excluding VAT, including the Climate Change Levy) give medium businesses 25.0p per kWh for electricity and 4.55p for gas. The Climate Change Levy main rate is the same for both fuels from 1 April 2026 (0.801p per kWh), so it does not favour either.

Boiler efficiency changes the answer a little, as this table of break-even SCOP at 25.0p electricity shows (these are assumptions for arithmetic, not measured efficiencies).

Assumed boiler efficiencyGas heat cost (p per kWh of heat)Break-even SCOP
85%5.35about 4.7
88%5.17about 4.8
90%5.06about 4.9

And for a heat pump at 25.0p electricity: SCOP 3.0 gives 8.33p per kWh of heat, SCOP 3.5 gives 7.14p, and SCOP 4.0 gives 6.25p. All are above the gas figures in the table, so at these national averages gas is cheaper on energy cost. One published installer guide reports a COP 3.2 system at 24p per kWh making heat at about 7.5p against 7-8p for a gas boiler, which implies a higher gas cost than the DESNZ average; the guide does not state its gas price. The honest reading is that the result depends on your tariffs. Use the calculator and your contract prices.

Capital, siting and supply

A like-for-like boiler swap usually reuses the plant room, flue, pipework and gas connection. A heat pump may need outdoor space or a roof lift, buffer storage, controls work and possibly a larger electrical supply. A connection upgrade from your distribution network operator can add cost and lead time, so ask early. Lower flow temperatures also help the SCOP, which can mean upgrading emitters. A hybrid arrangement that retains the boiler for the coldest days can reduce that work. Published installed-cost bands are in the cost guide.

Carbon, resilience and noise

A gas boiler’s emissions are set by the fuel it burns. A heat pump’s depend on the carbon intensity of the electricity supplied and the SCOP achieved, so any percentage saving someone quotes should come with those assumptions. If your electricity is partly self-generated or on a low-carbon contract, the case improves.

Maintenance deserves the same scrutiny as capital. A heat pump has no flue or combustion, but it has a refrigerant circuit, and refrigerant handling in the UK falls under F-Gas regulation and must be done by suitably qualified people. Refrigerants in use include R32, R290 (propane, which is flammable) and R744 (carbon dioxide), and the choice can affect where a unit may be sited. Ask each installer which refrigerant they propose, what the service plan covers and who responds to a fault.

On resilience, a heat pump relies on electricity and a gas boiler on gas. Neither is automatically more secure; a hybrid keeps both. Heat pump fans create outdoor noise, and for commercial premises the permitted-development rights for air-source units are written for dwellings, so check with the local planning authority. A noise assessment to BS 4142 is commonly requested.

Funding and tax tilt the comparison

A Boiler Upgrade Scheme grant of £7,500 (or £9,000 for oil or LPG off the gas grid, 21 July 2026 to 31 March 2027) is available only for heat pumps of 45 kW thermal or less for a single heat pump (70 kW thermal for a multi-unit system) in England and Wales, and the installer applies for it. Capital allowances can apply to either type of heating plant, but full expensing does not apply to heating systems; confirm with your accountant. The full picture is in grants and funding.

Comparison questions

Is a heat pump cheaper to run than a gas boiler for a business?

Only if its SCOP exceeds the break-even. At DESNZ Q1 2026 medium-business averages the break-even is about 4.8 against a boiler assumed at 88% efficiency. With cheaper electricity the break-even falls.

Does the Climate Change Levy favour heat pumps?

Not from 1 April 2026: the main rate is 0.801p per kWh for both electricity and gas.

Can I keep my gas boiler and add a heat pump?

Yes. A hybrid arrangement uses the heat pump for most of the load and the boiler for peaks. See the hybrid retrofit guide.

Which has lower carbon?

It depends on the grid carbon intensity and the SCOP. Ask for the assumptions behind any claim.

Keep reading

Request a commercial heat pump quote

Tell us about the building. We reply by email. This site is not an installer and cannot promise when.

  • 1. You send the form. The more you know about the building and its gas use, the more useful the reply.
  • 2. We reply by email. This site is an information service and does not promise a quote or a reply time.
  • 3. You choose. Ask for MCS and other credentials, compare written quotes and check installers on the public registers (for example mcscertified.com).

By submitting you agree to our privacy policy. Your details go to the site operator, who replies by email, and are processed by Formspree (USA); see the privacy policy for how long they are kept.

Sources

Request a quote
Request a quote